Auxiliary, trip and supervision relays

2L10 / 2L11 Battery Earth Fault Relays

Summary

Features

  • Wide range of battery voltages catered for
  • High sensitivity
  • 2L11 model differentiates between positive & negative earth faults
  • Low burden
  • Fast operate time
  • High output contact rating with optional magnetic arc blowouts
  • Optional hand reset flag
  • Size 2M draw out case

Application

Sub-station battery supplies are critical to the correct operation of critical protection & other functions. The 2L10 & 2L11 are designed to operate on earth faults or degradation of the insulation to earth of a battery or other DC supply which has neither pole connected to earth.
The relay earths the battery through a high resistance with a consequent limit to the earth fault current.
It should be noted that the relay will not operate for an earth fault to the centre of the battery.